Range of product | Modicon X80 |
Product or component type | Analog output module |
Electrical connection | 20 ways 1 connector |
Isolation between channels | Isolated |
Measurement error | <= 0.25 % of full scale 0...60 °C 0.1 % of full scale 25 °C |
Temperature drift | 45 ppm/°C +/- 10 V 45 ppm/°C 0...20 mA 45 ppm/°C 4...20 mA |
Common mode between channels | >= 80 dB |
Isolation voltage | 1400 V DC between channels and ground 1400 V DC between channels and bus 750 V DC between channels |
Detection type | Open circuit 0...20 mA Open circuit 4...20 mA Short circuit +/- 10 V |
Load impedance ohmic | >= 1000 Ohm +/- 10 V <= 500 Ohm 0...20 mA <= 500 Ohm 4...20 mA |
Output level | High level |
Analogue output number | 4 |
Analogue output type | Current: 0...20 mA Current: 4...20 mA Voltage: +/- 10 V |
Analogue output resolution | 15 bits + sign |
Supply | Internal power supply via rack |
Conversion time | <= 1 ms |
Maximum conversion value | 0...21 mA 0...20 mA 0...21 mA 4...20 mA +/- 10.5 V +/- 10 V |
Fallback mode | Configurable Predefined |
Protective treatment | TC |
Operating altitude | 0...2000 m 2000...5000 m with derating factor |
Status LED | 1 LED (green)RUN: 1 LED per channel (green)channel diagnostic: 1 LED (red)ERR: 1 LED (red)I/O: |
Net weight | 0.15 kg |
Power consumption in W | 3 W 24 V DC typical 3.2 W 24 V DC maximum 0.48 W 3.3 V DC typical 0.61 W 3.3 V DC maximum |
Analog 4 U/I Out Isolated